Take Apart Liquid Line Filter Drier - 2-5/8" ODF Connection
For 101 tons ~ R-134a or 107 tons ~ R407C applications.
At 30 deg C liquid refrigerant temperature.
Selection: PCN 037570, ADKS 400 21 T.
Maximum working pressure: 500psig
Filtration: 40 micron, with H100 blocks.
At 30 deg C liquid refrigerant temperature.
Selection: PCN 037570, ADKS 400 21 T.
Maximum working pressure: 500psig
Filtration: 40 micron, with H100 blocks.
Monday, June 02, 2008
Troubleshooting EPRBS Regulators
Problem A:
EPRBS regulator will not open.
Causes:
1) Excess dirt in pilot/ solenoid.
2) Piston bleed hole restriction.
3) Coil is damaged or not energized.
Corrective Action:
Disassemble valve and clean. Replace if necessary.
Verify coil is energized. Replaced if necessary.
EPRBS regulator will not open.
Causes:
1) Excess dirt in pilot/ solenoid.
2) Piston bleed hole restriction.
3) Coil is damaged or not energized.
Corrective Action:
Disassemble valve and clean. Replace if necessary.
Verify coil is energized. Replaced if necessary.